Maintenance Object Repair Procedures
555-233-123
10-210
Issue 4 May 2002
Signaling Link Board Check (#643)
This nondestructive test checks the health of the ATM TN230X trunk circuit pack
hardware. The test runs on a periodic or scheduled basis, during initialization
testing, and upon demand.
NOTE:
The board-level maintenance is handled independently of the ATM-CES
signaling link maintenance, raising the possibility of inconsistent states.
Table 10-75.
TEST #643 Signaling Link Board Check
Error
Code
Test
Result
Description/Recommendation
ABORT
Internal System Error
Retry the command at 1-minute intervals for a maximum of 5
times.
8
FAIL
The TN230X circuit pack is not in-service.
Check the Error Log for ATM-TRK errors and resolve any using
‘‘ATM-TRK (Circuit Emulation Service Circuit Pack)’’
PASS
The ATM TN230X circuit pack is in-service.
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...