Maintenance Object Repair Procedures
555-233-123
10-1360
Issue 4 May 2002
Table 10-502.
TEST #1281 TCP/IP Ping Test
Error
Code
Test
Result
Description/Recommendation
1, 2, 7,
11
ABORT
Internal error
1. Retry the command at 1-minute intervals up to 3 times
2. Escalate if the problem persists.
1005
ABORT
Test configuration is incorrect.
1. Verity PPP link is in-service (status clan-port UUCSSpp or
status link n).
2. Repeat the test.
3. Escalate if the problem persists.
1124
ABORT
ppp link is not enabled.
1. Verify that the ppp link is enabled (status port UUCSSpp,
status link n, or display data-module).
2. If the link is not enabled, enable the link (change
data-module).
3. Repeat the test.
4. Escalate if the problem persists.
1125
ABORT
PPP link not in service.
1. Verify whether ppp link is in service (status port UUCSSpp
or status link n).
2. If the ppp link is not in service, release the link (release link
n or release port UUCSSpp).
3. Repeat the test.
4. Escalate if the problem persists.
2000
ABORT
Response to the test was not received from the CLAN circuit
pack within the allowable time period.
1. If this result occurs repeatedly, attempt to reset the circuit
pack if the other ports on the board are not in use (Yellow
LED is off). Reset the circuit pack (busyout board UUCSS,
reset board UUCSS, and release board UUCSS).
2. If this result occurs again, replace the circuit pack.
2012
ABORT
Internal system error.
1. Retry the command at 1-minute intervals, up to 3 times.
2. Escalate if the problem persists.
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...