Maintenance Object Repair Procedures
555-233-123
10-1270
Issue 4 May 2002
Table 10-474.
TEST #572 Maintenance/Test Circuit Pack Query Test
Error
Code
Test
Result
Description/Recommendation
1006
ABORT
The Packet Bus port of the Maintenance/Test circuit pack is out
of service.
1. Determine if the port is busied out. If so, release the port by
entering the release port PCSS04 command. Re-enter the
test command.
1142
ABORT
No Maintenance/Test circuit pack Packet Bus port is in service in
this port network.
1. If this system has Critical Reliability, either (a) the
Maintenance/Test circuit pack for this port network has
failed, and should be replaced, (b) the Maintenance/Test
circuit pack has been busied out, and should be released, or
(c) there is no Maintenance/Test circuit pack in this port
network, and one must be installed.
2. In a system without Critical Reliability, the Maintenance/Test
Packet Bus Port may not be present. If the port is present,
and if it is busied out or has failed, release or replace the
circuit pack. If there is no Maintenance/Test circuit pack,
ignore the results of this test for this port network.
2000
ABORT
The test timed-out while waiting for an uplink CCMS response
from the Maintenance/Test Packet Bus port.
1. Retry the command at 1-minute intervals a maximum of 5
times.
2. If the test continues to abort, check for problems with the
Maintenance/Test Packet Bus port .
2059
ABORT
The Maintenance/Test Packet Bus port has reported a hardware
failure.
1. Re-enter the test command.
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...