Maintenance Object Repair Procedures
555-233-123
10-1720
Issue 4 May 2002
Standby Reference Health Check Test (#651)
This test evaluates the quality of the external synchronization timing source for the
Standby Tone-Clock circuit pack.
Table 10-634.
TEST #651 Standby Reference Health Check Test
Error
Code
Test
Result
Description/Recommendation
ABORT
This test may already be running due to a tone-clock
installation, scheduled maintenance, alarm activity, or a
technician-demand test from another terminal. This abort can
also occur due to an internal system error.
1. Try the command again at 1-minute intervals up to 5
times.
1184
ABORT
This test requires an external synchronization source to be
administered (DS1 primary, DS1 primary and secondary, or
Stratum 3 Clock).
1. Administer the external synchronization source and retry
the test.
2500
ABORT
Internal system error
1. Try the command again at 1-minute intervals up to 5
times.
0
FAIL
If the Tone-Clock circuit pack is in the PPN, the external
synchronization timing source for side A of the Stratum 3
clock, or for the Primary DS1 reference is either absent or
invalid. If the Tone-Clock circuit pack is in an EPN, the
synchronization reference from the active EI circuit pack is
either absent or invalid.
1
FAIL
If the Tone-Clock circuit pack is in the PPN, both external
synchronization timing sources are either absent or invalid. If
the Tone-Clock circuit pack is in an EPN, the
synchronization references from both EI circuit packs are
either absent or invalid.
1. Correct the synchronization source problem. Refer to the
Synchronization (SYNC) maintenance section of this
manual.
2. If the error still exists, replace the Tone-Clock circuit pack
reported in the error log.
PASS
The external synchronization timing source is valid.
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...