AC-POWER
Issue 4 May 2002
10-7
555-233-123
AC Power for DC-Powered Systems
NOTE:
For environment maintenance, the PPN or EPN cabinet configuration
aspects in a High or Critical Reliability system are irrelevant.
1
(cont)
FAIL
(cont)
2. Procedures for a Global MCC (J58890CH):
a. For a nominal holdover system if there is no AC power at
the wall outlet, then the problem is not with the system itself.
Power must be restored to the wall outlet.
b. If there is AC power at the wall outlet, then there could be a
problem with the Rectifiers (RM850), Battery Interface Unit,
or battery. Resolve all alarms logged against the POWER
Maintenance Object, and rerun the test. If the test still fails,
the BIU may be defective. Check to see if the BOD alarm
LED is “on”, on the BIU. If the BOD LED is “on” replace the
Battery Interface Unit (BIU). If the BOD LED is “off” and the
BOK LED is “on” then the SYSAM or the EPN Maintenance
circuit pack may be incorrectly reporting the problem.
Resolve all alarms against these Maintenance Objects and
rerun the test.
100
FAIL
The switch is currently without AC power, and AC Power
maintenance is in the middle of timing the NPH interval.
1. Follow the repair steps outlined above for Error Code 1.
PASS
The PR-MAINT (Maintenance/Tape Processor) in a PPN in a
system without High or Critical Reliability, the DUPINT (Duplication
Interface) circuit pack in a High or Critical Reliability system PPN, or
the EPN MAINT (Maintenance) circuit pack in an EPN multicarrier
cabinet system has reported that the switch has AC power. If there
is no AC power at the wall outlet, then look for and resolve all
alarms against the appropriate MO listed.
MO Name (in
Alarm Log)
Alarm
Level
Initial Command to Run
1
1
Where P is an appropriate port network number determined via the PORT field from the
Alarm or Error Log.
Full Name of MO
AC-POWER
WARNING
test environment P
AC Power
Table 10-2.
TEST #78 AC Power Query Test — Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...