POWER (Battery & Battery Charger for DC-Powered
Systems
Issue 4 May 2002
10-1351
555-233-123
2029
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5
times.
any
FAIL
The Duplication Interface circuit pack in a PPN for a high or
critical reliability system is incorrectly reporting a problem with
power. If this test fails, the problem is with the circuit pack and
not with POWER.
1. The suspect circuit pack, depending on the system
configuration, should be replaced and the test rerun.
PASS
All that can be inferred is that the DUPINT (Duplication
Interface) circuit pack in a PPN for a high or critical reliability
system is working properly.
Table 10-497.
TEST #5 Battery & Battery Charger Query Test — Continued
Error
Code
Test
Result
Description/Recommendation
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...