Maintenance Object Repair Procedures
555-233-123
10-422
Issue 4 May 2002
k. Error Type 3840—Port Audit and Update Test (#36) failed due to an
internal system error. Enter the status trunk command to verify the status
of the trunk. If the trunk is out-of-service, then enter the release trunk
command to put it back into in-service. Retry the test command. If the test
continues to abort, then escalate the problem.
System Technician-Demanded Tests: Descriptions
and Error Codes
Always investigate tests in the order they are presented in the table below when
inspecting errors in the system. By clearing error codes associated with the NPE
Crosstalk Test, for example, you may also clear errors generated from other tests
in the testing sequence.
For example, you may also clear errors generated from other tests in the testing
sequence.
NPE Crosstalk Test (#6)
One or more Network Processing Elements (NPEs) resides on each circuit pack
with a TDM Bus interface. The NPE controls port connectivity and gain, and
provides conferencing functions on a per-port basis. The NPE Crosstalk Test
verifies that this port’s NPE channel talks on the selected time slot and never
crosses over to time slots reserved for other connections. If the NPE is not
working correctly, one-way and noisy connections may be observed. This test is
usually only part of a port’s Long Test Sequence and takes about 20 to 30
seconds to complete.
Order of Investigation
Short Test
Sequence
Long Test
Sequence
D/ND
1
1
D = Destructive; ND = Nondestructive
NPE Crosstalk Test (#6)
X
ND
Conference Circuit Test (#7)
X
ND
DS1CO Trunk Seizure Test (#314)
X
X
ND
Port Audit and Update Test (#36)
X
X
ND
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...