STBY-SPE (Standby SPE)
Issue 4 May 2002
10-1523
555-233-123
NOTE:
When more than one of the above error types exists at the same time, the
alarm against the Standby SPE is cleared only when (1) any problems
described by the Aux Data values for Error Types 1 and 257 are resolved
and (2) all problems described in (b) through (o) are resolved.
Notes:
a. Aux Data value 0 is equivalent to Aux Data value 2017. All Aux Data values
listed for Error Type 1 are described in “System Technician-Demanded
Tests: Test Result Error Codes”. These values are shared between
Standby SPE maintenance activity results and the test results for the
System Technician commands on Standby SPE components because the
values represent the common set of problems that can be encountered
when attempting to conduct any form of maintenance activity on the
Standby SPE.
b. Error Type 58 is logged when the Duplication Interface circuit pack in the A
carrier reports that the Standby SPE has gone into Down Mode. This
implies an inability to communicate with the Standby SPE.
The ability to communicate with the Standby SPE should be checked by
issuing the test processor a | b short command, where “a | b” indicates
the carrier that contains the Standby SPE. If all of the tests execute such
that no test returns an Aux Data value of 2014, 2015, 2016, 2017, 2022,
2024, or 2025, the Standby SPE was successfully put into Maintenance
Mode. This indicates that the communication path between the Active SPE
and the Standby SPE may be functional. However, to restore the
functionality of the communication path, look for the presence of Error
Types 80, 81, and 106 and use the recommended commands to clear
these errors.
812 (y)
any
SPE interchanged
forced with
health-override option:
WRNG
OFF
See note (y).
822(z)
any
A non-hot interchange
to the standby SPE
occurred.
See note (z).
826
(aa)
any
Standby software
mismatch
MAJOR
ON
upgrade software
1
Run the short test sequence first. If all the tests pass, run the long test sequence. Refer to the
appropriate test description and follow the recommended procedures.
Table 10-576.
Standby SPE Error Log Entries — Continued
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...