status system
Issue 4 May 2002
8-395
555-233-123
BUS
ALARMS-MINOR
Whether Minor alarms exist for packet bus components (y/n)
BUS FAULTS
Number of faulty bus leads (defined as shorted to another
lead, stuck at some value, or an open lead: 0 - 24). This field
may take on any integer between 0 and 24. This field displays
blank if:
■
Maintenance/Test circuit pack not present
■
Packet Bus port of the Maintenance/Test circuit pack has
been taken out-of-service
■
System does not have the Packet Bus feature
OPEN BUS
LEADS
Number of open bus leads between the Maintenance/Test
circuit pack and bus terminator (0 - 24). This could mean
physical damage to the backplane or its connectors or a
missing bus terminator. This field displays blank if:
■
Maintenance/Test circuit pack is not present
■
Packet Bus port of the Maintenance/Test circuit pack has
been taken out-of-service
■
System does not have the Packet Bus feature.
EMERGENCY
TRANSFER
Location of the Processor or EPN Maintenance circuit pack
containing the Emergency Transfer Select Switch (
1A
and
1B
for the PPN, and
2A
or
3A
for the EPNs)
SELECT SWITCH
Emergency Transfer Switch position on the Processor(s) or
the EPN maintenance circuit pack and the state of
Emergency Transfer in the cabinet display:
■
on
: If this is a Simplex PPN or an EPN, then designated
analog phones in this cabinet are cut through to CO trunk
lines only in an emergency situation. In a High or Critical
Reliability System, the Emergency Transfer Switches on
both SPEs in the PPN must be in the on position before
Emergency Transfer is invoked for the PPN.
■
off
: Regardless of Simplex or Duplex, PPN, or EPN,
Emergency Transfer is off and cannot be invoked. The
switch should only be in this state when a service
technician is on sight.
■
auto-on
: The switch is in the or auto position, however,
because of a serious system fault, system software has
invoked Emergency Transfer.
■
auto-off
: Switch in the auto position; because system
has no serious faults, system software has not invoked
Emergency Transfer
■
unavail
: EPN is down
■
<blank> If the system is Simplex, then the 1B Emergency
Transfer indication for the PPN displays a blank. If the
system does not have an EPN, then both the 1A and 1B
Emergency Transfer indications for the EPN displays a
blank.
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...