CARR-POW (Carrier Port Power Unit) for AC-Powered
Systems
Issue 4 May 2002
10-373
555-233-123
2000
ABORT
Response to the test request was not received within the
allowable time period.
2029
ABORT
Internal System Error.
1. Retry the command at 1-minute intervals a
maximum of 5 times.
1 (Carrier E) 2
(Carrier D) 4
(Carrier A) 8
(Carrier B) 16
(Carrier C)
FAIL
There is a problem with one or both Power Unit(s) on the
recycled carrier.
1. Since the Power Unit Recycle Test failed, both
Power Units in the recycled carrier should have
been powered off by the system software. Both
power units should be showing a red status LED,
instead of a green one. Since the Power Unit Query
Test is a subset of the Power Unit Recycle Test, the
Power Unit Query Test (#127) should also fail. Run
the Power Unit Query Test by using the test
environment P command where P is the
appropriate port network number.
2. If the test fails, follow the repair procedures
described for Test #127. If problem persists, follow
normal escalation procedures.
PASS
Both power units in the recycled carrier were found to be
healthy by the Maintenance/Tape Processor in a
Standard system PPN, the Duplication Interface circuit
pack in a PPN for a system with High or Critical
Reliability, or the EPN Maintenance circuit pack in an
EPN multicarrier cabinet system after the power units
were powered down and back up. If the status LEDs on
both power units are not showing green, then the
PR-MAINT (Maintenance/Tape Processor), DUPINT
(Duplication Interface) circuit pack, or the EPN MAINT
(Maintenance) circuit pack may have incorrectly
reported the state of the power units. Look for and
resolve any alarms on these MOs.
Table 10-141.
TEST #126 Power Unit Recycle Test — Continued
Error Code
Test
Result
Description/Recommendation
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...