Maintenance Object Repair Procedures
555-233-123
10-1568
Issue 4 May 2002
16
FAIL
All power supplies failed.
1. Replace the failed power supplies.
2. If battery backup for the Stratum 3 clock is not supplied or
if the battery backup holdover time has been exceeded,
the system references the local oscillator on the Active
TN780 Tone-Clock circuit pack until software detects one
or both power supplies has(have) been restored
(approximately 40 minutes). To speed up this restoration,
issue the test synchronization r 4 command. All tests
should pass. If any repetitions should fail, follow the
procedures for those failures. If the problem persists after
you have performed this procedure three times, follow
normal escalation procedures.
32
FAIL
All clock unit(s) failed.
1. Look at the Stratum 3 cabinet for red LEDs on circuit
cards marked "ST3." Replace the card(s).
2. Determine if the alarm still exists by issuing the test
synchronization r 4 command to clear the alarm. If any
test repetitions fail, follow the procedure for those failures.
If the problem persists after you have performed this
procedure three times, follow normal escalation
procedures.
2101
FAIL
The TN780 Tone-Clock circuit pack detects loss of signal.
Refer to Note (b) of the STRAT-3 Hardware Error Log Entries
table in the STRAT-3 (Stratum 3 Clock) Maintenance
documentation for replacement procedures.
PASS
The Stratum 3 clock has reported that it has no alarm
conditions. If synchronization problems have been reported,
look for SYNC errors and refer to SYNC (Synchronization)
Maintenance documentation for recommended strategy for
those errors.
Table 10-580.
TEST #649 Stratum 3 Clock Alarm Query — Continued
Error
Code
Test
Result
Description/Recommendation
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...