
XXX-BD (Common Port Circuit Pack)
Issue 4 May 2002
10-2007
555-233-123
g. This error indicates transient communication problems with this circuit
pack. This error is not service-affecting and no action is required.
h. This error, when reported with Aux data in the range of 4352 to 4358,
indicates that the circuit pack has reported an on-board hardware failure.
The circuit pack continuously tests the hardware and report the results
approximately every 10 minutes. If the hardware problem is resolved, the
“leaky bucket” strategy should clear the alarm in approximately 30 minutes.
However, if the alarm does NOT clear in 30 minutes, the circuit pack should
be replaced.
i. This error can be ignored, but look for other errors on this circuit pack.
j. This error is not service-affecting and no action is required.
k. This error indicates that no ringing current is detected. Run Test #51,
Ringing Application Test, and follow the procedures for Test #51. This error
is only applicable to Analog Line circuit packs.
l. The hyperactive circuit pack is out-of-service and may exhibit one or more
of the following symptoms:
1. The common circuit pack level tests such as Test #51 and/or Test
#220 are aborting with error code 2000.
2. The tests run on the ports of this circuit pack are returning with a
NO-BOARD.
3. A busyout/release of the circuit pack has no affect on test results.
4. A list configuration command shows that the circuit pack and ports
are properly installed.
If the XXX-BD is not a TN754 Digital Line Circuit Pack (DIG-BD), and if this
error happens again within 15 minutes, replace the circuit pack. If the
XXX-BD is a TN754 Digital Line Circuit Pack (DIG-BD), check the alarm
level. If the alarm level is a WARNING, this indicates that users are
probably causing the hyperactivity by playing with their digital stations. If
the circuit pack is really hyperactive, this alarm is upgraded to a MINOR
alarm within one hour. If the alarm level is a MINOR alarm, replace the
circuit pack. (Refer to the
‘‘Handling Control Circuit Packs’’
section in
Chapter 5, ‘‘Routine Maintenance Procedures’’
m. This error indicates that no neon current is detected. Run Test #220, Neon
Test, and follow the procedures for Test #220. This error is applicable only
to TN769 and TN746 Analog Line circuit packs.
n. This error is not service-affecting and no action is required.
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...