SPE-SELEC (SPE Select Switch)
Issue 4 May 2002
10-1515
555-233-123
Table 10-575.
TEST #278 SPE Select Query Test
Error
Code
Test
Result
Description/Recommendation
1000
ABORT
System resources required to run this test are not available.
2000
ABORT
Response to the test request was not received within the
allowable time period.
2033
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5
times.
1
FAIL
The switch currently selects SPE-A active.
2
FAIL
The switch currently selects SPE-B active.
1. Move the switch to the AUTO position.
2. Rerun the test.
3
FAIL
The Duplication Interface circuit pack is not present or not
functioning.
1. Resolve all alarms logged against the Duplication Interface
circuit pack (DUPINT).
2. Rerun the test.
PASS
The Duplication Interface circuit pack has reported that the SPE
Select Switch is in the AUTO position.
1. If a visual inspection shows the SPE Select Switch is not in
the AUTO position, then resolve all alarms logged against
Duplication Interface circuit pack (DUPINT).
2. Repeat the test.
3. If Duplication Interface circuit pack B is being tested and a
visual inspection shows that the switch is not in the normal
position, Duplication Interface circuit pack A may be
incorrectly reporting the state of SPE-Select Switch B.
Replace Duplication Interface circuit pack A, and rerun the
test.
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...