E-DIG-BD (Multi Application Platform Board)
Issue 4 May 2002
10-721
555-233-123
E-DIG-BD (Multi Application
Platform Board)
The maintenance strategy for E-DIG-BD is the same as the one described for
XXX-BD. Maintenance testing of the common circuit pack is handled by on-board
firmware and SPE controlled tests. Maintenance software queries the firmware for
error and alarm information, status, and test results. The firmware automatically
reports error conditions that will result in SPE-controlled testing.
Board Insertion
The switch makes an additional board query if any of the following circuit packs
are inserted:
For any of the above initial board up-links, the switch sends queries requesting
additional data from the board for administration purposes, while also telling the
board the switch software release and the system type.
For the native mode, the response to the board query downlink messages
consists of several CCMS uplink messages that identify the true board code,
vintage, suffix, emulation type, and the number of reserved slots it needs.
Hyperactivity
The common circuit pack is considered “hyperactive” if the service dispatcher
receives 200 up-link messages from the circuit pack in a 10-second period. Since
MAPD has 32 ports, the hyperactivity limit is increased to 500 up-link messages
per 10seconds. An alarm is issued and the board taken out of service when the
limit reaches 400 or when it hits 500 up-link messages in 10 seconds.
MO Name (in
Alarm Log)
Alarm
Level
Initial Command to Run
1
1
Where P is the port network number (1 for PPN and 2 or 3 for EPN); C is the carrier
designation (for example, A, B, C, or D); and SS is the address of the slot in the
carrier where the circuit pack is located (for example, 01, 02, ...).
Full Name of MO
DIG800-BD
MIN
test board PCSS sh
MO800DIG-BD
DIG800-BD
WRN
test board PCSS sh
MO800DIG-BD
Circuit Pack
Vintage
TN754
49
TN556
49, 80 or greater
TN800
any
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...