Maintenance Object Repair Procedures
555-233-123
10-478
Issue 4 May 2002
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests: Descriptions
and Error Codes
There are no errors associated with the CPAD CUST-ALM MO. The test
customer-alarm PC command is provided to allow a technician to check that the
customer-provided alarming device is correctly installed and functional. It is
recommended that this test be run at least once after both the switch and the
customer alarm have been installed.
Always investigate tests in the order presented in the table below when inspecting
errors in the system. By clearing error codes associated with the
Customer-Provided Alarming Device Test, for example, you may also clear errors
generated from other tests in the testing sequence.
Customer-Provided Alarming Device Test (#115)
This test closes the relay that activates the CPAD for 1 minute only within the port
network specified. If it takes longer than 1 minute to check that the CPAD has
been activated, the Repeat field on the test customer-alarm PC command can
be used to close the relay for up to 99 minutes. Note that when the repeat option
is used, the results for Test #115 come back immediately and, for each test that
passed, the CPAD is kept on for that many minutes. The CPAD does not go off
after 1 minute and then come back on. Instead, the CPAD is kept on continuously
for the entire time. If the CPAD is being activated and deactivated in a flickering
fashion, there is a problem with either the CPAD, or the Maintenance/Tape
Processor, or the EPN Maintenance circuit pack.
Table 10-172.
Customer Provided Alarming Device Error Log Entries
Error Type
Aux Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
none
none
none
Order of Investigation
Short Test
Sequence
Long Test
Sequence
D/ND
1
1
D = Destructive; ND = Nondestructive
Customer-Provided Alarming Device Test (#115)
X
X
ND
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...