Maintenance Object Repair Procedures
555-233-123
10-1226
Issue 4 May 2002
b. The circuit pack has been logically administered but not physically
installed. If this alarm remains active for more than 30 minutes, follow
normal escalation procedures. DO NOT PHYSICALLY RESEAT THE
CIRCUIT PACK! The alarm is cleared when the circuit pack is installed and
initialization maintenance runs on it. The Standby Processor Interfaces
alarm is cleared when Standby maintenance runs on it.
c. Processor Interface-SCI detected an error while trying to reset the TN765
PI circuit pack. This error indicates a loss of communication with the circuit
pack. If this error continues, then replace the TN765 circuit pack. Refer to
Chapter 6, ‘‘Reliability Systems: A Maintenance Aid’’
for instructions on
how to replace an SPE complex circuit pack. See PI-SCI Maintenance
documentation for additional errors.
d. PI-SCI logged errors that resulted in an error being logged and an alarm
being raised against PI-BD. Refer to the PI-SCI Maintenance
documentation and resolve all alarms against PI-SCI. If this alarm resulted
in an SPE-interchange, issue the test interface PCS sh command to try to
resolve the PI-BD alarm.
e. A wrong circuit pack is inserted in the slot where this circuit pack is logically
administered. To resolve this problem, either remove the wrong circuit pack
and insert the logically administered circuit pack OR use the change
circuit-pack command to re-administer this slot to match the circuit pack
inserted.
f. This error indicates transient communication problems with this circuit
pack. This error is not service-affecting and no action is required.
g. This error, when reported with Aux Data in the range of 4352 to 4358,
indicates the circuit pack has reported a hardware failure on the circuit
pack. The circuit pack should be replaced. Refer to
for instructions on how to replace an SPE
complex circuit pack.
h. This error can be ignored, but look for other errors on this circuit pack.
i. This error is not service-affecting and no action is required.
j. The hyperactive circuit pack is out-of-service and may exhibit one or more
of the following symptoms:
1. The common circuit pack level tests such as Test #51 and/or Test
#220 are aborting with Error Code 2000.
2. The tests run on the ports of this circuit pack are returning with a
NO-BOARD.
3. A list configuration command shows that the circuit pack and ports
are properly installed.
The system tries to restore the circuit pack within 15 minutes. If the error
recurs after 15 minutes, replace the circuit pack. (Refer to the “Handling
Control Circuit Packs” section in
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...