TONE-PT (Tone Generator)
Issue 4 May 2002
10-1813
555-233-123
Tone Generator Crosstalk Test (#90)
This test checks the ability of the Tone Generator to talk on a specific time slot.
The tone generator is told to talk on a specific time slot. The other idle time slots
are checked to make sure the Tone Generator put the tone on only the specified
time slot.
Table 10-659.
TEST #90 Tone Generator Crosstalk Test
Error
Code
Test
Result
Description/Recommendation
None
ABORT
Internal System Error
1. Retry the command at 1-minute intervals a maximum of 5
times.
2. If the test continues to abort, follow normal escalation
procedures.
1001
ABORT
The system was not able to put the tone generation facility in the
appropriate mode to test it.
1002
ABORT
The system could not allocate time slots for the test connection.
This can happen when the system is heavily loaded. If the system
is not heavily loaded, then test the TDM-BUS via test tdm
port-network PN# . Refer to TDM-BUS section for details.
2000
ABORT
Response to the test request was not received within the allowable
time period.
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5
times.
2. If the test continues to abort, follow normal escalation
procedures.
FAIL
The Tone Generator could be defective. In a Port Network with
more than one Tone-Clock circuit pack, the system will attempt to
move the tone generation function to the alternate one.
1. Test the Tone-Clock circuit pack again via test tone-clock PC.
2. If the test fails again, look at the Hardware Error Log for Tone
Detector circuit pack errors.
3. If there are Tone Detector circuit pack errors, refer to Tone
Detector Maintenance documentation (DTMR-PT, GPTD-PT,
CLAS-PT, ETR-PT) to resolve these errors first.
4. If there are no Tone Detector circuit pack errors, then the
Tone-Clock circuit pack should be replaced. See
Replace a Tone-Clock Circuit Pack’’
.
PASS
The tone generation facility is able to put tones out.
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...