Maintenance Object Repair Procedures
555-233-123
10-10
Issue 4 May 2002
Table 10-5.
TEST #78 AC Power Query Test
Error
Code
Test
Result
Description/Recommendation
1000
ABORT
System resources required to run this test are not available.
2000
ABORT
Response to the test request was not received within the allowable time
period.
2029
ABORT
Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
any
FAIL
The Maintenance/Tape Processor in a PPN in a system without High or
Critical Reliability, the Duplication Interface circuit pack in a High or Critical
Reliability system PPN, or the EPN Maintenance circuit pack in an EPN
multicarrier cabinet system is incorrectly reporting a problem with AC power.
If this test fails, the problem is with the circuit pack and not with
AC-POWER. The suspect circuit pack, depending on the system
configuration, should be replaced and the test rerun.
PASS
All that can be inferred is that the PR-MAINT (Maintenance/Tape Processor)
in a PPN in a system without High or Critical Reliability, the DUPINT
(Duplication Interface) circuit pack in a High or Critical Reliability system
PPN, or the EPN MAINT (Maintenance) circuit pack in an EPN multicarrier
cabinet system is working properly.
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...