Table 93: Application nominal current relation to the upper limit of linear
measurement range
Application nominal
current (I
n
)
Rated secondary value
with 80A / 0.150 V at 50
Hz (0.180 V at 60 Hz)
Upper limit of linear
measurement range
40...800 A
1.500...30.000 mV/Hz
60 × I
n
800...1250 A
30.000...46.875 mV/Hz
60...40 × I
n
1250...2500 A
46.875...93.750 mV/Hz
40...20 × I
n
2500...4000 A
93.750...150.000 mV/Hz
20...12.5 × I
n
shows the upper limits of the linear measurement range based
on a certain range in application nominal current. The linear measurement
limit for a given application nominal current can be derived from the values
stated in the table with a simple proportion equation. For example, the
upper limit for linear measurement for 3000 A application nominal current
would be 17.5 xIn.
It can also be calculated from
that with the stated sensor the relay
input can linearly measure up to 50 kA (RMS) short circuit currents.
Rogowski sensor and overcurrent protection setting evaluation example
A 20 kV utility substation with a single busbar switchgear rated up to 40
kA shortcircuit currents has one incomer and 20 outgoing feeder relays
using 80 A/0.150 V at 50 Hz Rogowski current sensors with rating plate
values similar to
. For the incomer panel, electrical system designer
has evaluated the application nominal current to be 1250 A. Customer
specification for these protection relays defines normal instantaneous and
time-delayed overcurrent and earth-fault protection functions. Overcurrent
protection requires functions to be settable up to 20 xIn.
The sensor setting
Primary current is set to be the same as the evaluated
application nominal current 1250 A. According to the sensor’s technical data,
the application nominal current matches the sensor’s capability which is up
to 4000 A.
The setting
Rated secondary value is calculated by using
.
1250
80
150
50
46 875
A
A
mV
Hz
mV
Hz
.
= .
(Equation 3)
From
it is seen that with the 1250 A application nominal current
value, the maximum setting for overcurrent protection is 40 xIn. This covers
the customer specification requirements for overcurrent settings of up to 20
xIn.
Voltage sensor setting example
The voltage sensor is based on the resistive divider or capacitive divider
principle. Therefore, the voltage is linear throughout the whole measuring
range. The output signal is a voltage, directly proportional to the primary
1MRS759142 F
Basic functions
REX640
Technical Manual
159
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......