second until the output is reset to FALSE. The output remains in this state until the
Home button is pressed again.
The output signal
WOKEN
is activated whenever the HMI device is woken from a
low-power state. This generates a one-second boolean TRUE value pulse. After one
second, the output is reset to FALSE. A new output can be triggered once the HMI
has entered the low-power state.
The output
CONNECTION
is activated whenever the paired HMI is connected to the
protection relay. If the communication between the protection relay and the HMI is
severed, this output resets itself to FALSE until communication has been restored.
When an SHMI is connected and paired with the protection relay, the
CONNECTION
output is activated when the user navigates from the SHMI navigation page to
the HMI view. The
CONNECTION
output is deactivated when the user returns to
the navigation view or the connection between the relay and the SHMI is lost. The
output can be used to visually indicate that the SHMI is connected to the relay in the
panel, and it works as an LHMI for the relay.
The output
ALM_ACKED
is activated when any alarms are acknowledged either by
the boolean rising edge on the
ALM_ACK
input or by acknowledging alarms from the
HMI. This generates a one-second boolean TRUE value pulse. After one second, the
output is reset to FALSE until some alarms are acknowledged. There is at least a
100 ms FALSE state between each pulse. If alarms are acknowledged from the HMI
during the TRUE state or within 100 ms after resetting to FALSE, additional pulses
are not be produced.
PCM600 parameters
EIHMI contains three paths to populate parameters visible in Parameter Setting in
PCM600.
• Configuration > HMI
• Monitoring > Detached LHMI
• Information > HW modules > EIHMI1
3.26.4
Application
Substation HMI wake-up (door sensor)
In this example, substation HMI devices need to be woken up when a person
enters the substation to see that everything works as expected.
A switch signal is directly connected to the binary input, which activates the
paired HMI.
Depending on the hardware solution, this hardware signal can be distributed
to all affected protection relays on the substation. Optionally, the processed
signal can be routed in horizontal communication through process bus
communications, that is, GOOSE, to other protection relays.
1MRS759142 F
Basic functions
REX640
Technical Manual
321
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......