Figure 524: Average operate time of DSTPDIS according to IEC 60255-121 network
models Short line and Long line (50 Hz)
SIR curves are plotted from the data which includes variation of fault location (0…
100% of zone reach, 5% step), fault type (LN, LL, LLN, LLL) and fault inception angle
(0, 30, 60, 90 degrees). Each combination has been repeated ten times giving the
total number of 26880 shots. The operate times include the delay of relay output
contacts. The SIR curves presented in
were obtained using the static
power outputs (SPOs) and with
Zone timer mode = "common".
4.7.1.4
Analog channel configuration
DSTPDIS has five analog group inputs which must be properly configured.
Table 904: Analog inputs
Input
Description
I3P
Three-phase currents
I3P_PAR
1
Three-phase currents
Necessary when
Par line Comp zone x
is set
to True
I3P_REF
2
Three-phase currents
Table continues on the next page
1
Can be connected to
GRPOFF
if
Par line Comp zone x is set to False.
2
Can be connected to
GRPOFF
if
EF detection Mod GFC is not set to "Io AND IoRef"
1MRS759142 F
Protection functions
REX640
Technical Manual
943
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......