The last measured and maximum travel time are stored in nonvolatile memory and
these values are not cleared until the reset input (RST_TRV_ T) is set to TRUE or reset
from the clear menu.
When the measured opening travel time is longer than the value set with the
Open
alarm time setting, the
TRV_T_OP_ALM
output is activated. Respectively, when the
measured closing travel time is longer than the value set with the
Close alarm time
setting, the
TRV_T_CL_ALM
output is activated.
It is also possible to block the TRV_T_CL_ALM and TRV_T_OP_ALM alarm signals by
activating the
BLOCK
input.
7.2.5
Application
Earthing switches or disconnectors are usually located either in metal- clad draw
out switchgear or outside in switch yard or pole mounted pole mounted. These
switches are operated on no load when circuit breaker is opened. Mechanical
actuation is affected due to continued exposure of varying weather conditions.
Supervision of following parameters helps understanding the mechanical condition
and need for maintenance:
• Increasing contact travel time might be indication e.g., of mechanical wear or
lubrication problem.
• Certain maintenance actions are dependent on operation counter value.
• Mechanism may be stuck if switch is in same position long period of time.
Inactivity time measurement guides operator for periodic movement.
7.2.6
Signals
7.2.6.1
ESDCSSWI Input signals
Table 1316: ESDCSSWI Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block all the alarm
and lockout indica-
tions
POSOPEN
BOOLEAN
0=False
Signal for open po-
sition of apparatus
from I/O
POSCLOSE
BOOLEAN
0=False
Signal for close po-
sition of apparatus
from I/O
OPEN_EXE
BOOLEAN
0=False
Signal for open com-
mand to coil
CLOSE_EXE
BOOLEAN
0=False
Signal for close com-
mand to coil
RST_TRV_T
BOOLEAN
0=False
Reset input for switch
closing and opening
travel times
Condition monitoring functions
1MRS759142 F
1380
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......