Figure 635: Natural unbalance compensation. (a) Healthy condition when the natural
unbalance is recorded (b) Unbalance compensation during faulty conditions
The natural unbalance compensation for each phase is enabled based on the
settings
Natural Comp Ena PhA, Natural Comp Ena PhB and Natural Comp Ena PhC
respectively. For example, if
Natural Comp Ena PhA is set to “FALSE”, the unbalance
current is not compensated. If
Natural Comp Ena PhA is set to “TRUE”, the
compensated unbalance current for phase A is calculated based on the equation.
I
I
I
CompUnb_A
Unb_A
NatUnb_A
=
−
(Equation 288)
I
CompUnb_A
Phase A-compensated unbalance current
I
Urb_A
Phase A-measured unbalance current
I
NatUnb_A
Phase A-recorded natural unbalance current
The phasewise-compensated unbalance current amplitudes and angles
I_COM_AMPL_A
,
I_COM_ANGL_A
,
I_COM_AMPL_B
,
I_COM_ANGL_B
,
I_COM_AMPL_C
and
I_COM_ANGL_C
are available in the monitored data view.
The phase angles of the unbalance currents indicate the branch of a faulty element
in a capacitor bank. For an internal fuse capacitor bank, the element failure branch
location is determined based on the phase angle of the compensated unbalance
current.
Table 1077: Detection of element failure location for internal fuse capacitor bank
Name of the phase angle
Phase angle of unbalance cur-
rent
Element failure branch loca-
tion
I_COM_ANGL_A
~+180°
Phase A - Branch 1 or Phase A
- Branch 4
I_COM_ANGL_A
~0°
Phase A - Branch 2 or Phase A
- Branch 3
Table continues on the next page
Protection functions
1MRS759142 F
1134
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......