currents by controlling the generator excitation system. If the AVR is out of service
or if there is an internal fault in the operation of AVR, the low fault currents can go
unnoticed and therefore a voltage-depended overcurrent protection should be used
for backup.
Two voltage control characteristics, voltage step and voltage slope, are available
in PHPVOC. The choice is made based on the system conditions and the level of
protection to be provided.
Voltage step characteristic is applied to generators used in industrial systems.
Under close-up fault conditions when the generator terminal voltages drop below
the settable threshold value, a new start value of the current, well below the normal
load current, is selected. The control voltage setting should ensure that PHPVOC
does not trip under the highest loading conditions to which the system can be
subjected. Choosing too high a value for the control voltage may allow an undesired
operation of the function during wide-area disturbances. When the terminal voltage
of the generator is above the control voltage value, the normal start value is used.
This ensures that PHPVOC does not operate during normal overloads when the
generator terminal voltages are maintained near the normal levels.
Voltage slope characteristic is often used as an alternative to impedance protection
on small to medium (5...150 MVA) size generators to provide backup to the
differential protection. Other applications of the voltage slope characteristic
protection exist in networks to provide better coordination and fault detection
than plain overcurrent protection. The voltage slope method provides an improved
sensitivity of overcurrent operation by making the overcurrent start value
proportional to the terminal voltage. The current start value varies correspondingly
with the generator terminal voltages between the set voltage high limit and voltage
low limit, ensuring the operation of PHPVOC despite the drop in fault current value.
The operation of PHPVOC should be time-graded with respect to the main
protection scheme to ensure that PHPVOC does not operate before the main
protection.
4.1.3.7
Signals
PHPVOC Input signals
Table 416: PHPVOC Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
ENA_MULT
BOOLEAN
0=False
Enable signal for cur-
rent multiplier
ENA_LOW_LIM
BOOLEAN
0=False
Enable signal for volt-
age dependent lower
start value
1MRS759142 F
Protection functions
REX640
Technical Manual
375
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......