
communication channel operating in direct intertripping applications should be
secure and dependable.
Setting guidelines for the intertrip scheme DUTT
•
Scheme type = "Intertrip"
•
Coordination Time = "0.050" s (10 ms + maximal transmission time)
•
Carrier Min Dur = "0.1" s
Permissive underreaching transfer trip PUTT
In the permissive underreach scheme, the permission to trip is obtained locally
from the underreaching zone and sent to the remote end. The received signal is
combined with the local fault indication from the overreaching zone resulting in a
trip command after a settable pick-up delay
Coordination Time.
The protection relay of either feeder end sends a permissive signal to trip the
other end. The communication channel must be able to receive and transmit at
the same time. In permissive schemes, the communication channel must be fast
and secure, but also dependable. Inadequate security causes unwanted tripping for
the external faults. Inadequate speed or dependability causes delayed tripping for
internal faults.
The
CS_PRM
signal is issued based on the underreaching zone Z1.
The underreach scheme is not applicable on short feeder lengths because the
impedance measurement cannot easily distinguish between the internal and
external faults in such cases.
The underreaching zones Z1 at the local and remote ends must overlap to prevent
a gap between the protection zones, where the faults are not detected. If the
underreaching zone does not meet the required sensitivity, for example, the
fault infeed from a remote end, the blocking or permissive overreach scheme is
considered.
To achieve an instantaneous trip, the carrier received signal
CR_PRM
must be
received when the overreaching zone Z2 is still starting. In some cases, due to a fault
in current distribution, the overreaching zone can operate only after the fault has
been cleared by the remote terminal. In this case, there is a risk that if the remote
terminal is tripped directly by, for example, zone Z1, the
CR_PRM
signal issued by the
zone resets before the overreaching zone of the local end terminal has operated.
To assure a sufficient duration of the
CR_PRM
signal, the
CR_PRM
signal can be
prolonged by the time
Carrier Min Dur. The recommended value of the Carrier Min
Dur setting is "0.1" s.
The received communication signal is combined with the output from the local
overreaching zone. Therefore, there is less concern about a false signal causing
an incorrect trip, and therefore the timer
Coordination Time is set to "0". A
communication channel failure does not affect the selectivity, but delays the
tripping at the other end for certain fault locations.
Setting guidelines for the permissive underreach scheme PUTT
•
Scheme type = "Permissive Underreach"
•
Coordination Time = "0" s
•
Carrier Min Dur = "0.1" s
Protection related functions
1MRS759142 F
1246
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......