MINCB_OPEN
DISCON_OPEN
Negative
phase
sequence
criterion
Current and
voltage
delta
criterion
I
2
I3P
I_C
I_B
I_A
BLOCK
Voltage
check
CB_CLOSED
U_A_AB
U3P
U
2
U_C_CA
U_B_BC
Decision
logic
FUSEF_3PH
FUSEF_U
Figure 758: Functional module diagram
Negative phase-sequence criterion
A fuse failure based on the negative-sequence criterion is detected if the measured
negative-sequence voltage exceeds the set
Neg Seq voltage Lev value and the
measured negative-sequence current is below the set
Neg Seq current Lev value.
The detected fuse failure is reported to the decision logic module.
Voltage check
The phase voltage magnitude is checked when deciding whether the fuse failure is a
three, two or a single-phase fault.
The module makes a phase-specific comparison between each voltage input and
the
Seal in voltage setting. If the input voltage is lower than the setting, the
corresponding phase is reported to the decision logic module.
Current and voltage delta criterion
The delta function can be activated by setting the
Change rate enable parameter
to "True". Once the function is activated, it operates in parallel with the negative
sequence-based algorithm. The current and voltage are continuously measured in all
three phases to calculate:
• Change of voltage dU/dt
• Change of current dI/dt
The calculated delta quantities are compared to the respective set values of the
Current change rate and Voltage change rate settings.
The delta current and delta voltage algorithms detect a fuse failure if there is a
sufficient negative change in the voltage amplitude without a sufficient change in
1MRS759142 F
Supervision functions
REX640
Technical Manual
1333
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......