4.2.8.2
Function block
Figure 312: Function block
4.2.8.3
Functionality
The third harmonic-based stator earth-fault protection H3EFPSEF is used to detect
stator earth fault at the neutral point and at least up to 15...20% from the neutral
point along the stator winding. H3EFPSEF compares the third harmonic voltages
produced by the generator itself at both neutral and terminal side of the generator
for detecting earth fault.
H3EFPSEF provides two alternative protection methods:
• Differential of the third harmonic component measured both at generator
neutral and terminal side
• Neutral side third harmonic undervoltage
H3EFPSEF operates with the definite time DT characteristics.
H3EFPSEF contains a blocking functionality. Blocking deactivates all outputs and
reset timers.
4.2.8.4
Analog channel configuration
H3EFPSEF has three analog group inputs which must be properly configured.
Table 602: Analog inputs
Input
Description
U3P
1
Three-phase voltages Necessary when
Volt-
age selection
is set to "Uo", "Phase A", "Phase
B" or "Phase C"
URES
2
Residual voltage (measured or calculated)
Necessary when
Voltage selection
is set to
"Uo"
UNEUT
Residual voltage (measured or calculated)
See the preprocessing function blocks in this document for the possible
signal sources. The
GRPOFF
signal is available in the function block called
Protection.
There are a few special conditions which must be noted with the configuration.
1
Can be connected to
GRPOFF
if
Voltage selection is set to "No voltage" or "Uo".
2
Can be connected to
GRPOFF
if
Voltage selection is other than "Uo".
Protection functions
1MRS759142 F
542
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......