Name
Type
Values (Range)
Unit
Description
Transfer duration
FLOAT32
0.0...200000.0
ms
Time between transfer
initiation and CB close
command
Busbar Max dv/dt
FLOAT32
-100.00...100.00
Maximum rate of
change of busbar volt-
age
Busbar Max df/dt
FLOAT32
-100.00...100.00
Maximum rate of
change of frequency of
busbar voltage
Busbar voltage
FLOAT32
0.0...10.0
Busbar voltage at the
time of CB close com-
mand
Busbar frequency
FLOAT32
35.00...75.00
Hz
Busbar frequency at the
time of CB close com-
mand
Phase difference
FLOAT32
-180.0...180.0
deg
Busbar and standby
feeder phase diff at CB
close command
CB decoupled
BOOLEAN
0=False
1=True
CB decoupling hap-
pened during the trans-
fer
Loadshed operated
BOOLEAN
0=False
1=True
Load shedding operat-
ed during transfer
9.12.10
Technical data
Table 1615: HSABTC Technical data
Characteristic
Value
Operation
accuracy
Voltage
±1.5% of the set value or ±0.002 × Un, frequency range
±10Hz
Frequency
±25mHz of the set value
Initiation time
Minimum
Typical
Maximum
Under voltage
1, 2, 3
14 ms
18 ms
21 ms
Under frequency
2, 3, 4
47 ms
49 ms
50 ms
External (binary in-
put)
2, 3, 5
9 ms
10 ms
12 ms
Initiation time accuracy
±20 ms of the set value
Operate time accuracy
±1.0% of the set value or ±20 ms
1
Start val Voltage = 0.95 × Un, voltage before fault = 1.0 × Un, fault voltage = 0.9 × set Start
val Voltage, undervoltage in one phase-to-phase voltage with nominal frequency injected from
random phase angle
2
Measured with static power output (SPO)
3
Results based on statistical distribution of 1000 measurements
4
Applies to continuous frequency change. If frequency change ≥ 0.5Hz (disturbance in network or
due to test setup), then initiation time is increased with 100ms to prevent false reaction.
5
Excluding the delay of the external triggering device
Control functions
1MRS759142 F
1806
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......