
Figure 230: Effect of the Weighting factor p factor and the difference between the
two time constants and one time constant models
The actual temperature of the transformer is calculated by adding the ambient
temperature to the calculated temperature.
Θ
Θ
Θ
= ∆
+
amb
(Equation 37)
Θ
temperature in transformer (°C)
ΔΘ
calculated temperature rise (°C) in transformer
Θ
amb
set value of the
Env temperature Set
setting or measured ambient tempera-
ture
The ambient temperature can be measured with RTD measurement. The measured
temperature value is connected, for example, from the
AI_VAL3
output of the X130
RTD function to the
AMB_TEMP
input of T2PTTR.
The
Env temperature Set setting is used to define the ambient temperature if
the ambient temperature measurement value is not connected to the
AMB_TEMP
input. The
Env temperature Set setting is also used when the ambient temperature
measurement connected to T2PTTR is set to “Not in use” in the X130 RTD function.
The temperature calculation is initiated from the value defined with the
Initial
temperature and Max temperature setting parameters. The initial value is a
percentage of
Max temperature defined by Initial temperature. This is done when
the protection relay is powered up or the function is turned off and back on or reset
through the Clear menu. The temperature is stored in a nonvolatile memory and
restored if the protection relay is restarted.
The
Max temperature setting defines the maximum temperature of the transformer
in degrees Celsius (°C). The value of the
Max temperature setting is usually given by
1MRS759142 F
Protection functions
REX640
Technical Manual
393
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......