the HV side voltage constant despite of variations in the load current and the MV
side voltage. This is achieved by monitoring the HV side voltage.
“Bi-dir(meas)” or “Bi-dir(calc)” set values should be used only when it is
clear that the source of reverse power flow is a strong source.
If HV side measurements are directly available, “Bi-dir(meas)” mode can be used. If
it is not available, “Bi-dir(calc)” can be set and HV side values are calculated (after
power reversal) from MV side measurements with the help of settings
Step of tap,
Tap nominal and Impedance voltage as given below.
If
Raise block tap > Lower block tap, then HV side voltage and current are calculated
as
= 1 + (
_
−
_
) ∗ ∆
∗ {
−
∗
}
}
{
(Equation 380)
1 + (
_
−
_
) ∗ ∆
=
}
{
(Equation 381)
If
Raise block tap < Lower block tap, then HV side voltage and current are calculated
as
= 1 + (
_
−
_
) ∗ ∆
∗ {
−
∗
}
}
{
(Equation 382)
=
1 + (
_
−
_
) ∗ ∆
}
{
(Equation 383)
U
HV
HV side voltage which will be compared with control voltage U
p
for HV side
regulation
I
HV
HV side current
U
MV
MV side measured voltage
I
MV
MV side measured current
TAP_NOM
Tap nominal
TAP_POS
Own tap position
ΔU
step
Step of Tap
ZV
Impedance voltage referred to MV side
When “Bi-dir(calc)” set value is used, it is mandatory that own tap
position information should be connected.
Since it is not always possible to know the source strengths on either side of
the transformer, an additional setting option “Auto select” is also provided. If
the
Regulation mode is set as “Auto select”, the direction of regulation will be
automatically selected by OL5ATCC function as below. A power ratio factor (PRF) is
calculated by the OL5ATCC function utilizing HV and MV side voltage and current
1MRS759142 F
Control functions
REX640
Technical Manual
1713
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......