
Figure 962: The 10-minute interval with time synchronization and free running 3
seconds
The 10-minute mean value is shown in the monitored data until the next 10-minute
mean value has been cumulated. Another 10-minute calculation might be started
when time synchronization is used to change the protection relay's internal clock.
The first calculation continues for 10 minutes and is then seen in the monitored data
with a time stamp. An event is sent every time a 10-minute value calculation is ready
in the monitored data.
See the Time synchronization chapter in this document.
When the protection relay is powered on, the shown value is zero until the first
10- minute mean value has been cumulated. During this time, the 10-minute output
quality is marked questionable in the IEC 61850 data.
When the settings
Reference Cur Sel or Demand current are changed, older data
is not cleared. Although older data is calculated based on different setting values,
those can still be used as they are used to calculate mean values. The influence
might be seen in mean values. These are considered as minor adjustments to the
reference current, similar to varying fundamental current.
Changing setting
Sliding interval has influence on the seen mean values. Sliding
values change slowly towards the input value during the time interval. When mean
values have not been calculated for a full interval, quality is marked questionable in
the IEC 61850 data. Questionable quality is also indicated for a full interval if the
protection relay is reset.
10.1.6
Application
Typically, the measured short-time 3-second mean values are used with a suitable
logic to give alarms. If a more stabilized value is needed, a 1-minute or 5-minute
mean value should be selected.
One example of using short-time mean values is to compare the level of THD and
some harmonics, for example, 5
th
and 7
th
. The values to be compared to the same
limit can be combined with MAX3R, and MAPGAPC can be used to test if the settable
limit value is exceeded. Outputs of MAPGAPC can be connected to the needed logic
and, for example, an event can be sent with MVGAPC.
The 10-minute mean values can be collected to an external substation monitoring
system. Collected data can be used in weekly reporting. If longer mean values are
needed, the collected 10-minute mean values can be used to calculate, for example,
two-hour mean values.
Power quality measurement functions
1MRS759142 F
1812
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......