Level detector
The module compares differential currents
I_A
calculated by the peak-to-peak
measurement mode to the set
Operate value. The Timer module is activated if the
differential current exceeds the value of the
Operate value setting.
Timer
Once activated, Timer activates the
START
output. The time characteristic is
according to DT. When the operation timer reaches the value set by
Minimum
operate time, the
OPERATE
output is activated. If the fault disappears before
the module operates, the reset timer is activated. If the reset timer reaches the
value set by
Reset delay time, the operation timer resets and the
START
output is
deactivated.
Timer calculates the start duration
START_DUR
value, which indicates the
percentage ratio of the start situation and the set operating time. The value is
available in the Monitored data view.
The activation of the
BLOCK
input resets Timer and deactivates the
START
and
OPERATE
outputs.
Blocking logic
There are three operation modes in the blocking functionality. The operation
modes are controlled by the
BLOCK
input and the global setting Configuration >
System > Blocking mode which selects the blocking mode. The
BLOCK
input can be
controlled by a binary input, a horizontal communication input or an internal signal
of the protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operation timer is frozen to the prevailing value. In the "Block all" mode,
the whole function is blocked and the timers are reset. In the "Block OPERATE
output" mode, the function operates normally but the
OPERATE
output is not
activated.
4.3.6.6
Application
HIxPDIF provides a secure and dependable protection scheme against all types of
faults. The high-impedance principle is used for differential protection due to its
capability to manage the through-faults also with the heavy current transformer
(CT) saturation.
For current transformer recommendations, see the Requirements for
measurement transformers section in this manual.
High-impedance principle
The phase currents are measured from both the incoming and the outgoing feeder
sides of the busbar. The secondary of the current transformer in each phase is
connected in parallel with a protection relay measuring branch. Hence, the relay
measures only the difference of the currents. In an ideal situation, there is a
differential current to operate the relay only if there is a fault between the CTs,
that is, inside the protected zone.
1MRS759142 F
Protection functions
REX640
Technical Manual
775
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......