Operation mode
Description
If the frequency restores before the module operates, the
reset timer is activated. If the timer reaches the value set
by the
Reset delay Tm Freq
setting, the operate timer resets
and the
START
and
STR_OFRQ
outputs are deactivated.
df/dt
The function operates independently as the frequency gra-
dient ("df/dt"), rate-of-change, protection function. When
the frequency gradient exceeds the set value of the
Start
value df/dt
setting, the module activates the
START
and
STR_FRG
outputs. The time characteristic is according to
DT. When the operation timer has reached the value set by
the
Operate Tm df/dt
setting, the
OPERATE
and
OPR_FRG
outputs are activated. If the frequency gradient restores be-
fore the module operates, the reset timer is activated. If the
timer reaches the value set by the
Reset delay Tm df/dt
set-
ting, the operate timer resets and the
START
and
STR_FRG
outputs are deactivated.
Freq< + df/dt
A consecutive operation is enabled between the protection
methods. When the measured frequency is below the set
value of the
Start value Freq<
setting, the frequency gradi-
ent protection is enabled. After the frequency has dropped
below the set value, the frequency gradient is compared to
the set value of the
Start value df/dt
setting. When the fre-
quency gradient exceeds the set value, the module activates
the
START
and
STR_FRG
outputs. The time characteristic is
according to DT. When the operation timer has reached the
value set by the
Operate Tm df/dt
setting, the
OPERATE
and
OPR_FRG
outputs are activated. If the frequency gradient
restores before the module operates, the reset timer is acti-
vated. If the timer reaches the value set by the
Reset delay
Tm df/dt
setting, the operate timer resets and the
START
and
STR_FRG
outputs are deactivated. The
OPR_UFRQ
out-
put is not active when this operation mode is used.
Freq> + df/dt
A consecutive operation is enabled between the protection
methods. When the measured frequency exceeds the set val-
ue of the
Start value Freq>
setting, the frequency gradient
protection is enabled. After the frequency exceeds the set
value, the frequency gradient is compared to the set value of
the
Start value df/dt
setting. When the frequency gradient
exceeds the set value, the module activates the
START
and
STR_FRG
outputs. The time characteristic is according to
DT. When the operation timer has reached the value set by
the
Operate Tm df/dt
setting, the
OPERATE
and
OPR_FRG
outputs are activated. If the frequency gradient restores be-
fore the module operates, the reset timer is activated. If the
timer reaches the value set by the
Reset delay Tm df/dt
set-
ting, the operate timer resets and the
START
and
STR_FRG
outputs are deactivated. The
OPR_OFRQ
output is not active
when this operation mode is used.
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
923
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......