Integrator box
Amplifier
Protection relay
Rogowski
coil
I
I>
Figure 251: Rogowski coil measurement arrangement
It is also possible to feed shaft current, measured with CT, directly to the relay
current input. Proper signal levels need to be ensured for reaching acceptable
operation accuracy.
Setting
Alarm start value and Operate start value
The current level that causes damage to bearings depends on the contact surface of
the bearings. Current densities over 0.1 A/mm
2
start to damage the bearings. This
can be generalized so, that currents over 1 A can be considered harmful. Therefore,
the recommended setting for
Operate start value is 0.5 A and for Alarm start value
0.25 A. Both values are set in primary amperes.
4.1.12.7
Signals
GSLPTOC Input signals
Table 496: GSLPTOC Input signals
Name
Type
Default
Description
ISHFT
SIGNAL
-
Analog input
BLOCK
BOOLEAN
0=False
Block signal for all bi-
nary outputs
GSLPTOC Output signals
Table 497: GSLPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
ALARM
BOOLEAN
Alarm
Protection functions
1MRS759142 F
438
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......