Phase-to-phase under-voltage criterion
Monitoring of the magnitude of any phase-to-phase voltage (U
AB
, U
BC
or U
CA
) and
comparing it to setting
XC stage PP V Val during a detected earth fault:
(Equation 135)
During a single-phase earth fault phase-to-phase voltages are not affected, but
during a cross-country fault the phase-to-phase voltages are affected, refer to
. Default setting for
XC stage PP V Val is 0.9xU
n_PP
, where U
n_PP
is the
nominal phase-to-phase voltage.
In case all three phase-to-phase voltages (U
AB
, U
BC
and U
CA
) are under
setting for
XC stage PP V Val , such condition is considered as permanent
three phase under-voltage condition, not a cross-country fault.
Figure 356: Illustration of behavior of residual, phase-to-earth and phase-to-phase
voltages during an evolvement of single-phase earth fault into cross-country fault in
a 10 kV compensated network
The magnitude of phase-to-phase voltage between faulted phases during a cross-
country fault can be estimated using the following equation:
1MRS759142 F
Protection functions
REX640
Technical Manual
627
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......