I
eFd
Magnitude of the earth-fault current of the protected feeder when the fault resist-
ance is zero ohm
I
eTot
Magnitude of the uncompensated earth-fault current of the network when Rf is
zero ohm
K
Compensation degree, K = 1 full resonance, K<1 undercompensated, K>1 overcom-
pensated
I
Rn
Rated current of the neutral earthing resistor
shows that in case of a fault inside the protected feeder in unearthed
networks, the measured admittance equals the admittance of the background
network. The admittance is dominantly reactive; the small resistive part of the
measured admittance is due to the leakage losses of the background network.
Theoretically, the measured admittance is located in the first quadrant in the
admittance plane, close to the im(Yo) axis, see
.
shows that in case of a fault inside the protected feeder in
compensated networks, the measured admittance equals the admittance of the
background network and the coil including the parallel resistor. Basically, the
compensation degree determines the imaginary part of the measured admittance
and the resistive part is due to the parallel resistor of the coil and the leakage
losses of the background network and the losses of the coil. Theoretically, the
measured admittance is located in the first or fourth quadrant in the admittance
plane, depending on the compensation degree, see
Before the parallel resistor is connected, the resistive part of the
measured admittance is due to the leakage losses of the background
network and the losses of the coil. As they are typically small, the
resistive part may not be sufficiently large to secure the discrimination
of the fault and its direction based on the measured conductance. This
and the rating and the operation logic of the parallel resistor should be
considered when setting the admittance characteristic in compensated
networks.
shows that in case of a fault inside the protected feeder in high-
resistance earthed systems, the measured admittance equals the admittance of
the background network and the neutral earthing resistor. Basically, the imaginary
part of the measured admittance is due to the phase-to-earth capacitances of the
background network, and the resistive part is due to the neutral earthing resistor
and the leakage losses of the background network. Theoretically, the measured
admittance is located in the first quadrant in the admittance plane, see
Protection functions
1MRS759142 F
496
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......