
if the estimated busbar phasor, after advance angle adjustment, lies in the zone Z2,
defined by the area under the curve AEFB.
Figure 953: Trajectory of phase-angle in relation to time
shows the trajectory of phase angle between stand-by feeder and
busbar and voltages and time after main supply feeder opening. It is shown
for various linear rates of frequency difference between the stand-by feeder and
busbar, assuming main supply feeder and stand-by feeders were in synch and the
frequency difference is zero prior to circuit breaker opening for main supply feeder.
FBBM transfer mode is suitable for setups having low frequency difference and rate
of change of frequency difference between the stand-by and busbar voltage.
First phase coincidence mode attempts to transfer at the 1
st
phase coincidence,
differential voltage minimum, between the stand-by feeder and busbar voltages
through anticipatory computation. It estimates the phase angle difference between
the stand-by feeder and busbar voltage ahead of CB closing time keeping into
account the prevailing frequency difference and rate of change of frequency
difference between the stand-by and busbar voltage. It attempts to transfer such
that phase angle difference is zero (ideally zero, practically near zero) after stand-
by feeder is completely closed. First phase coincidence transfer can occur if the
estimated busbar phasor, after anticipatory calculation, lies in the zone Z3.
Residual mode attempts to transfer if busbar voltage magnitude drops below
predefined setting,
Res voltage limit. Residual transfer can occur if the busbar
phasor lies in the zone Z4, represented by the area under the inner most circle with
radius
Res voltage limit.
Application variants
The following different variants, depending on various circuit breaker
configurations, can be realized with the instances of this function.
1MRS759142 F
Control functions
REX640
Technical Manual
1791
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......