
1. Settings
Reduction factor and Maximum earthing Ris are used to scale the
estimated effective earth-fault current value into corresponding touch voltage
or earth-potential rise estimate.
2. Setting
UTp multiplier enables operation based on permissible earth potential
rise U
E
, by scaling of the permissible time-touch voltage characteristics given in
standard EN 50522 with Setting
UTp multiplier, see table below.
Table 632: Permissible touch voltages U
Tp
and earth potential rise U
E
values
as a function of the fault duration t
f
according to standard EN50522 with U
Tp
multiplier as a parameter
Fault duration t
f
[sec.]
Permissible touch
voltage, U
Tp
, U
Tp
multiplier = 1.0 [V]
Permissible earth
potential rise, U
E
,
U
Tp
multiplier = 2.0
[V]
Permissible earth
potential rise, U
E
,
U
Tp
multiplier = 4.0
[V]
0.05
716
1432
2864
0.10
654
1308
2616
0.20
537
1074
2148
0.50
220
440
880
1.00
117
234
468
2.00
96
192
384
5.00
86
172
344
10.00
85
170
340
3. Minimum touch voltage or earth potential rise magnitude (considering the
effect of
Reduction factor), which must be exceeded for the function to start, is
defined with setting
Touch Vol Str Val. It is important to set setting Touch Vol
Str Val according to required protection sensitivity.
4. With
IDMT stage Min Op Tm setting user can define minimum allowed operate
time for IFPTOC i.e. this is the minimum allowed operate time of IFPTOC.
5. With
IDMT stage Max Op Tm setting user can define maximum allowed operate
time for IFPTOC i.e. this is the maximum allowed operate time of IFPTOC
although IDMT timer would define slower operate time.
Parameter defining maximum earthing resistance, setting
Maximum
earthing Ris must be always set in case Operation principle = “Touch
voltage based” and
Operating curve type = “Inverse time EN50522” is
selected. Setting
Maximum earthing Ris is needed to scale the estimated
effective earth-fault current value to corresponding touch voltage or
earth potential rise value.
Setting
Reduction factor considers the fact that only part of the earth-
fault current (I
F
) will flow back through “remote” earth and introduces
earthing and touch voltages.
Minimum practical value for setting
Touch Vol Str Val is 0.5% of
CT primary current multiplied by setting
Maximum earthing Ris. For
example, in case CT primary current is 200 A, and
Maximum earthing
Ris = 10 ohm, then minimum practical value for setting Touch Vol Str
Val is 0.5%*200 A*10 ohm = 10 V. For CT with 400 A primary current,
then minimum practical value for setting
Touch Vol Str Val is 0.5%*400
A*10 ohm = 20 V. The lower setting
Touch Vol Str Val is used, the
higher sensitivity in terms of fault resistance can be obtained. Sensitivity
1MRS759142 F
Protection functions
REX640
Technical Manual
615
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......