Table 1418: CSMSQI Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Ps Seq A on delay
time
0...1800000
ms
100
0
Delay the activa-
tion of the alarm
and warning out-
puts for positive
sequence current
Ps Seq A off delay
time
0...1800000
ms
100
0
Delay the deactiva-
tion of the alarm
and warning out-
puts for positive
sequence current
Ng Seq A on delay
time
0...1800000
ms
100
0
Delay the activa-
tion of the alarm
and warning out-
puts for negative
sequence current
Ng Seq A off delay
time
0...1800000
ms
100
0
Delay the deactiva-
tion of the alarm
and warning out-
puts for negative
sequence current
Zro A on delay time 0...1800000
ms
100
0
Delay the activation
of the alarm and
warning outputs
for zero sequence
current
Zro A off delay time 0...1800000
ms
100
0
Delay the deactiva-
tion of the alarm
and warning out-
puts for zero se-
quence current
8.1.11.7
CSMSQI Monitored data
Table 1419: CSMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
NgSeq-A:1
FLOAT32
0.00...40.00
xIn
Measured negative se-
quence current
PsSeq-A:1
FLOAT32
0.00...40.00
xIn
Measured positive se-
quence current
ZrSeq-A:1
FLOAT32
0.00...40.00
xIn
Measured zero se-
quence current
I2_HIGH_AL
BOOLEAN
0=False
1=True
Negative sequence high
alarm
I2_HIGH_WARN
BOOLEAN
0=False
1=True
Negative sequence high
warning
I1_HIGH_AL
BOOLEAN
0=False
1=True
Positive sequence high
alarm
I1_HIGH_WARN
BOOLEAN
0=False
1=True
Positive sequence high
warning
I1_LOW_WARN
BOOLEAN
0=False
1=True
Positive sequence low
warning
I1_LOW_AL
BOOLEAN
0=False
1=True
Positive sequence low
alarm
I0_HIGH_AL
BOOLEAN
0=False
1=True
Zero sequence high
alarm
Table continues on the next page
Measurement functions
1MRS759142 F
1474
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......