4.1.5.6
Application
The lines and cables in the power system are constructed for a certain maximum
load current level. If the current exceeds this level, the losses will be higher than
expected. As a consequence, the temperature of the conductors will increase. If the
temperature of the lines and cables reaches too high values, it can cause a risk of
damages by, for example, the following ways:
• The sag of overhead lines can reach an unacceptable value.
• If the temperature of conductors, for example aluminium conductors, becomes
too high, the material will be destroyed.
• In cables the insulation can be damaged as a consequence of overtemperature,
and therefore phase-to-phase or phase-to-earth faults can occur.
In stressed situations in the power system, the lines and cables may be required
to be overloaded for a limited time. This should be done without any risk for the
above-mentioned risks.
The thermal overload protection provides information that makes temporary
overloading of cables and lines possible. The thermal overload protection estimates
the conductor temperature continuously. This estimation is made by using a
thermal model of the line/cable that is based on the current measurement.
If the temperature of the protected object reaches a set warning level, a signal is
given to the operator. This enables actions in the power system to be done before
dangerous temperatures are reached. If the temperature continues to increase to
the maximum allowed temperature value, the protection initiates a trip of the
protected line.
4.1.5.7
Signals
T1PTTR Input signals
Table 434: T1PTTR Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
BLK_OPR
BOOLEAN
0=False
Block signal for oper-
ate outputs
ENA_MULT
BOOLEAN
0=False
Enable Current multi-
plier
AMB_TEMP
FLOAT32
0
The ambient temper-
ature used in the cal-
culation
1MRS759142 F
Protection functions
REX640
Technical Manual
387
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......