
In-zone transformer
20kV
300A/1
1500A/1
PROTECTED
ZONE
110kV
Yd11
40MW
HV
LV
L
~
RED 615
RED 615
Figure 382: In-zone transformer example about CT ratio correction calculation
The CT ratio correction calculation starts with the rated load current calculation
for HV and LV sides. The rated load current is defined as the rated power of the
transformer divided by the square root of three times the nominal phase-to-phase
voltage at the HV or LV side.
I
S
U
nT
n
n
=
×
3
(Equation 156)
The rated load current of the transformer on the HV side is 209.9 A (40 MW / (√3 ×
110 kV)) and the rated load current of the transformer on the LV side is 1154.7 A (40
MW / (√3 × 20 kV)). This means that the CT ratio corrections for the HV and LV sides
are:
CT ratio correction (HV) = 1.429 (300 A / 209.9 A)
CT ratio correction (LV) = 1.299 (1500 A / 1154.7 A)
Small power transformers in a tap
With a relatively small power transformer in a line tap, the line differential protection
can be applied without the need of current measurement from the tap. In such
cases, the line differential function is time delayed for low differential currents
below the high set limit and LNPLDF coordinates with the downstream protection
relays in the relevant tap. For differential currents above the set limit, the operation
is instantaneous. As a consequence, when the load current of the tap is negligible,
the low resistive line faults are cleared instantaneously at the same time as
maximum sensitivity for the high resistive faults are maintained but with a time
delayed operation. The maximum sensitivity for high resistive faults is maintained at
the same time, but with a time delayed operation.
1MRS759142 F
Protection functions
REX640
Technical Manual
673
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......