does not, however, reset the counters holding the blockings, so the blocking signals
may return when these conditions are not valid anymore.
External blocking functionality
TR2PTDF has three inputs for blocking.
• When the
BLOCK
input is active ("TRUE"), the operation of the function is blocked
but measurement output signals are still updated.
• When the
BLK_OPR_LS
input is active ("TRUE"), TR2PTDF operates normally
except that the
OPR_LS
output is not active or activated in any circumstance.
Additionally, the
OPERATE
output can be activated only by the instantaneous high
stage (if not blocked as well).
• When the
BLK_OPR_HS
input is active ("TRUE"), TR2PTDF operates normally
except that the
OPR_HS
output is not active or activated in any circumstance.
Additionally, the
OPERATE
output can be activated only by the biased low stage
(if not blocked as well).
4.3.2.6
Application
TR2PTDF is a unit protection function serving as the main protection for
transformers in case of winding failure. The protective zone of a differential
protection includes the transformer, the bus-work or the cables between the current
transformer and the power transformer. When bushing current transformers are
used for the differential protection relay, the protective zone does not include the
bus work or cables between the circuit breaker and the power transformer.
In some substations, there is a current differential protection for the busbar. The
busbar protection includes bus work or cables between the circuit breaker and the
power transformer. Internal electrical faults are very serious and cause immediate
damage. Short circuits and earth faults in windings and terminals are normally
detected by the differential protection. If enough turns are short-circuited, the
interturn faults, which are flashovers between the conductors within the same
physical winding, are also detected. The interturn faults are the most difficult
transformer-winding faults to detect with electrical protections. A small interturn
fault including a few turns results in an undetectable amount of current until the
fault develops into an earth fault. Therefore, it is important that the differential
protection has a high level of sensitivity and that it is possible to use a sensitive
setting without causing unwanted operations for external faults.
It is important that the faulty transformer is disconnected as fast as possible. As
TR2PTDF is a unit protection function, it can be designed for fast tripping, thus
providing a selective disconnection of the faulty transformer. TR2PTDF should never
operate to faults outside the protective zone.
TR2PTDF compares the current flowing into the transformer to the current leaving
the transformer. A correct analysis of fault conditions by TR2PTDF must consider
the changes to voltages, currents and phase angles. The traditional transformer
differential protection functions required auxiliary transformers for the correction
of the phase shift and turns ratio. The numerical microprocessor based differential
algorithm implemented in TR2PTDF compensates for both the turns ratio and the
phase shift internally in the software.
The differential current should theoretically be zero during normal load or external
faults if the turns ratio and the phase shift are correctly compensated. However,
there are several different phenomena other than internal faults that cause
Protection functions
1MRS759142 F
694
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......