
Master/Follower principle M/F
The M/F operation principle is suitable for power transformers with identical
ratings and step voltages. One voltage regulator (master) measures and controls
and the other regulators (followers) follow the master, that is, all the tap changers
connected in parallel are synchronized. This parallel operation is obtained by
connecting the
FLLWx_CTL
output of the master to the corresponding OLGAPC
function input
TR_TAP_FLLW
of the followers via horizontal GOOSE communication.
The values for the
FLLWx_CTL
command are 1=Lower follower x and 2=Raise
follower x. Consequently, the values for OLGAPC function
TR_TAP_FLLW
command
are 1=Lower and 2=Raise.
If several regulators act as masters (one at a time), their outputs also have to be
routed to the inputs of the other regulators. To start the parallel operation, the
master regulator is set to the "Auto master" mode and the followers to the "Auto
follower" mode. A regulator acting as a follower can be set to master in three ways.
• Activating input
MSTR_TRIGG
if
Parallel mode is set to "Input control"
• Activating MstrOp via communication if
Parallel mode is set to "Command"
• Activating the Master Trig button in the LHMI control dialog for OL5ATCC if
Parallel mode is set to "Command"
The regulator indicates its master status (“Independent”, “Master” or “Follower”)
by the TR_STATUS monitored data. A parallel regulator, previously acting as master,
receives this signal via the
TR_STATUS
input of OLGAPC and changes its status to
follower.
Connect the
TR_STATUS
input to the OLGAPC of the parallel transformer
and route the
TR_DAT
output from OLGAPC to OL5ATCC
TRx_DAT
for proper M/F functionality. If
TR_STATUS
is left unconnected, that
particular parallel transformer is assumed to not be participating even
though receiving valid tap position information.
To keep all the tap changers in the same position, the master needs to know
the tap positions of the followers. This way, the circulating current is kept at its
minimum. The position values of the followers can be brought to the master either
via horizontal GOOSE communication or TPOSYLTC.
If it is not possible to use horizontal communication between the protection relays
and the position information cannot be wired from the parallel transformers,
the M/F principle can still be used to regulate two or an unlimited number of
transformers in parallel. Since the master cannot detect the tap positions of parallel
transformers, it just activates the lowering and raising outputs for all the followers
when it controls its own tap changer. This is called blind control. In this case, a
number of parallel transformers are regulated as one unit.
The combined data inputs
TRx_DAT
must be left unconnected for the master to
know that the tap positions of the followers are unknown. The time delay between
successive commands can be set by the
Follower delay time setting. The default
value is 6 seconds.
When a disconnected transformer is taken into use and the tap position is unknown,
it is recommended that the follower should be manually controlled to the same
position as the master. In the M/F mode, the master gives its own transformer
a control command which is echoed to the followers (the follower's tap positions
must be connected). Thereafter, successive control commands to the followers take
place until the master and followers have the same tap positions.
1MRS759142 F
Control functions
REX640
Technical Manual
1707
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......