Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.12.4.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are “On” and “Off”.
The operation of SRCPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Level
detector 1
RESO_IN
BLOCK
ALARM
OPERATE
Level
detector 2
Blocking
logic
Resonance
current
calculation
I3P
I_A
I_B
I_C
t
Timer 1
t
Timer 2
Figure 639: Functional module diagram
Resonance current calculation
This module calculates the resonance current per phase set as per setting
Tuning
harmonic Num. The resonance current for phase A is calculated with the equation.
I
RESO
A
I
I
I
I
RMS
A
A
DC
A
K
A
_
_
_
_
_
_
=
−
−
−
2
1
2
2
2
(Equation 289)
I
RMS_A
RMS value of current in phase A (contains up to 11
th
harmonic)
I
DC_A
DC-component in phase A current
I_A
Fundamental component in phase A current
I
K_A
K
th
harmonic component in phase A current, K is defined by setting
Tuning
harmonic Num
I_RESO_A
Calculated resonance current for phase A
The resonance current is calculated through the filter implementation. The DC and
fundamental components are removed by passing the total RMS current through
the High pass filter. The K
th
harmonic component is removed by passing the
High pass filter output through the K
th
harmonic Band stop filter. The magnitude
1MRS759142 F
Protection functions
REX640
Technical Manual
1143
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......