4.7.3.8
UEXPDIS Settings
Table 951: UEXPDIS Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Diameter
1...6000
%Zn
1
200
Diameter of the
Mho diagram
Offset
-1000...1000
%Zn
1
-10
Offset of top of
the impedance cir-
cle from the R-axis
Displacement
-1000...1000
%Zn
1
0
Displacement of
impedance circle
centre from the X-
axis
Operate delay time 60...200000
ms
10
5000
Operate delay time
Table 952: UEXPDIS Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Restraint enable
0=Disable
1=Enable
0=Disable
Enable restrain
area
Rst offset X
-1000...1000
%Zn
1
0
Offset of direction-
al line from origin
along X-axis
Rst offset X angle
-180.0...180.0
deg
0.1
-13.0
Angle between R-
axis and directional
line
Table 953: UEXPDIS Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
External Los Det
Ena
0=Disable
1=Enable
1=Enable
Enable external ex-
citation loss detec-
tion
Voltage reversal
0=No
1=Yes
0=No
Rotate voltage sig-
nals by 180 degrees
Impedance Meas
mode
1=1Phase-to-earth
2=1Phase-to-phase
3=3Phase-to-earth
4=3Phase-to-phase
5=Pos sequence
5=Pos sequence
Select voltage and
currents for impe-
dance calculation
Phase Sel for Z Clc
1=A or AB
2=B or BC
3=C or CA
1=A or AB
Voltage phase se-
lection
Table 954: UEXPDIS Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
3000
Reset delay time
Protection functions
1MRS759142 F
1024
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......