transferring the possible additional blocking information between the local and
remote terminals whenever the blocking logic behavior needs to be the same on
both line ends.
Test mode
The line differential function in one protection relay can be set to test mode, that
is, the
Operation setting is set to “test/blocked”. This blocks the line differential
protection outputs in the protection relay and sets the remote protection relay to a
remote test mode, such that the injected currents are echoed back with the shifted
phase. It is also possible that both protection relays are simultaneously in the test
mode. When the line differential protection function is in the test mode:
• The remote end protection relay echoes locally injected current samples back
with the shifted phase. The current samples that are sent to the remote
protection relay are scaled with the CT ratio correction setting.
• The operation of both stages (stabilized low or instantaneous high) are blocked,
and also the direct inter-trip functionality is blocked (both receive and send) in
the protection relay where the test mode is active.
• The remote end line differential protection function that is in the normal mode
(On) is not affected by the local end being in the test mode. This means that the
remote end function is operative but, at the same time, it ignores the received
current samples from the other end protection relay which is in the test mode.
• The
PRO_ACTIVE
output is false only in the protection relay that is currently in
the test mode.
Figure 375: Operation during the normal operation of the line differential protection
Protection functions
1MRS759142 F
664
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......