
Level detector 1
The measured rotor earth-fault current (DFT value) is compared to the
Operate start
value setting. If the measured value exceeds that of the Operate start value setting,
Level detector 1 sends a signal to start the Timer 1 module.
Level detector 2
The measured rotor earth-fault current (DFT value) is compared to the set
Alarm
start value. If the measured value exceeds that of the Alarm start value setting, Level
detector 2 sends a signal to start the Timer 2 module.
For MREFPTOC, the earth-fault current is the current that flows due to
the voltage injected by the injection device in the rotor circuit when an
earth fault arises.
A considerable amount of harmonics, mainly 3rd and 6th, can occur in the
excitation current under normal no-fault conditions, especially with the
thyristor excitation and rotating diode rectifier systems. MREFPTOC uses
DFT value calculation to filter DC and harmonic components which could
otherwise give out false alarms or trips.
Timer 1
Once activated, the Timer activates the
START
output. The timer characteristic is
according to DT. When the operation timer has reached the value set by
Operate
delay time in the DT mode, the
OPERATE
output is activated. If a drop-off situation
occurs, that is, a fault suddenly disappears before the operating delay is exceeded,
the timer reset state is activated. The reset time depends on the
Reset delay time
setting.
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates all outputs and resets the internal timers.
Timer 2
Once activated, the Timer activates the alarm timer. The timer characteristic is
according to DT. When the alarm timer has reached the value set by
Alarm delay time
in the DT mode, the
ALARM
output is activated. If a drop-off situation occurs, that is,
a fault suddenly disappears before the alarm delay is exceeded, the timer reset state
is activated. The reset time depends on the
Alm reset delay time setting.
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates all outputs and resets the internal timers.
4.2.5.6
Application
The rotor circuit of synchronous machines is normally isolated from the earth. The
rotor circuit can be exposed to an abnormal mechanical or thermal stress due to, for
example, vibrations, overcurrent and choked cooling medium flow. This can result
in the breakdown of the insulation between the field winding and the rotor iron
at the point exposed to excessive stress. If the isolation resistance is decreased
significantly, this can be seen as an earth fault. For generators with slip rings, the
rotor insulation resistance is sometimes reduced due to the accumulated carbon
dust layer produced by the carbon brushes. As the circuit has a high impedance to
earth, a single earth fault does not lead to any immediate damage because the fault
current is small due to a low voltage. There is, however, a risk that a second earth
1MRS759142 F
Protection functions
REX640
Technical Manual
517
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......