
Figure 506: Typical example of operation of LVRTPTUV function
Activation of the
BLOCK
input resets the timers and deactivates the function
outputs.
4.5.8.6
Application
Distributed generation, mainly wind and solar farms, are rapidly increasing due
to liberalized markets (deregulation) and the global trend to use more renewable
sources of energy. These farms are directly connected to grids, and due to their
large size may influence the behavior of the grid. These farms are now required
to comply with stringent grid connection requirement, which was previously
mandatory only for high capacity power plants. These requirements include helping
grid in maintaining system stability, reactive power support, transient recovery and
voltage-frequency regulation. These requirements make it necessary for the wind
and solar farms to remain in operation in the event of network disturbances.
Many grid codes now demand that the distributed generation connected to HV
grids must withstand voltage dips to a certain percentage of nominal voltage (down
to 0% in some cases) and for a specific duration. Such requirements are known as
Low-Voltage Ride-Through (LVRT) or Fault-Ride-Through (FRT) and are described by
a voltage versus time characteristics.
Typical LVRT behavior of a distributed generation can be divided into three areas
according to the variation in voltage over time.
• At the time of system faults, the magnitude of the voltage may dip to
Voltage
level 1 for time defined by Recovery time 1. The generating unit has to remain
connected to the network during such condition. This boundary defines area A.
Protection functions
1MRS759142 F
904
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......