Figure 288: Forward directional oversusceptance characteristic. Left figure: classical
forward directional oversusceptance criterion. Middle figure: characteristic is tilted
with negative tilt angle. Right figure: characteristic is tilted with positive tilt angle.
Combined overadmittance and overconductance characteristic
The combined overadmittance and overconductance criterion is enabled with the
Operation mode setting set to "Yo, Go" and Directional mode to "Non-directional".
The characteristic is a combination of a circle with the radius defined with the
Circle radius setting and two overconductance boundary lines with the settings
Conductance forward and Conductance reverse. For the sake of application
flexibility, the midpoint of the circle can be moved from the origin with the
Circle
conductance and Circle susceptance settings. Also the boundary lines can be tilted
by the angle defined with the
Conductance tilt Ang setting. By default, the Circle
conductance and Circle susceptance are 0.0 mS and Conductance tilt Ang equals
zero degrees, that is, the characteristic is a combination of an origin-centered
circle with two vertical overconductance boundary lines. A positive tilt value for
the
Conductance tilt Ang setting rotates boundary lines counterclockwise from the
vertical axis.
In case of the non-directional conductance criterion, the
Conductance reverse
setting must be set to a smaller value than
Conductance forward.
Operation is achieved when the measured admittance moves outside the
characteristic.
The combined overadmittance and overconductance criterion is applicable in
unearthed, high-resistance earthed and compensated networks or in systems
where the system earthing may temporarily change during normal operation from
compensated network to unearthed system.
Compared to the overadmittance criterion, the combined characteristic improves
sensitivity in high-resistance earthed and compensated networks. Compared to the
non-directional overconductance criterion, the combined characteristic enables the
protection to be applied also in unearthed systems.
Protection functions
1MRS759142 F
506
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......