function is blocked and the timers are reset. In the “Block OPERATE output” mode,
the function operates normally but the
OPERATE
output is not activated.
4.5.10.6
Application
Overvoltage in a network occurs either due to the transient surges on the network
or due to power frequency overvoltages. Surge arresters are used to protect
the network against the transient overvoltages; power frequency overvoltage
of magnitude greater than 15...20% of nominal voltage is normally handled by
traditional overvoltage protection. However, slow voltage variations are usually
quantified by calculating the RMS value of the voltage. To assess the RMS voltage,
measurements are taken over a relatively long period of time to avoid any
instantaneous effect caused by switching transients or faults.
It is important to monitor such slow voltage variation which can cause sub-optimal
operation of the equipment. EN 50160 quantifies slow voltage variation using 10
min mean RMS value. CEI EN 50160 standard indicates that the RMS value of the
voltage calculated over a period of 10 min should not exceed 110% of the nominal
voltage; if the voltage exceeds this level, the generator must be disconnected from
the network within 3 s. PHVPTOV provides overvoltage protection by calculating the
RMS value over a period of 10 min.
A sudden change in the magnitude of the supply voltage is not immediately
detected by the RMS calculation; hence this is mainly used as an indication of
voltage quality supplied by the utility.
4.5.10.7
Signals
PHVPTOV Input signals
Table 872: PHVPTOV Input signals
Name
Type
Default
Description
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
INITIALIZE
BOOLEAN
0=False
Initialize the volt-
age average measure-
ment
RESET
BOOLEAN
0=False
Reset the volt-
age average measure-
ment values
PHVPTOV Output signals
Table 873: PHVPTOV Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
Protection functions
1MRS759142 F
918
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......